Static Regulator 500 KVA

General Features

- Advanced Technology

- High Reliability with Full Digital Microprocessor Control

- Wide Power Options in Mono Phase and Three Phase Systems

- Wide Input Voltage Range

- True RMS Measurement and Feedback, Control

- Best in Class with 5000 V/s Regulation Speed

- Regulation in 1 period with 20 ms response time

- EMI / RFI Filter (Optionally)

- Overload, Over Voltage, Low Voltage Protections

- Lightning Protection (Optionally)

- Short Circuit Protection

- Izolation Transformer (Optionally)

- Harmonic Filter (Optionally)

- Manuel By-Pass

- Automatic Operation in Abnormal Conditions

- Independent Phase Operation

- High Performance Even on 100% Unbalanced Load

- Silent Operation, High Efficiency and Sensibility

- Modular, Ergonomic Design

- 100% Made in TURKEY

- Environmental Design

- Small Dimensions, Silent Operation

- Easy Installation/Maintenance and Service

- Low Installation and Operational Costs

- 10 Years Spare Part Warranty

- 7/24 Technical Service and Customer Services

 

Optional Features

- Custom Design and Production for Client’ s Need

- Remote Monitoring and Management Options

 

Standards

- CE, ISO 9001:2008

Model

Static Regulator

Power

500 kVA

INPUT

Operating Voltage Range

200 – 400 / 240 – 420 / 275 - 450 VAC

Working Voltage Range

155 - 490 VAC

Frequency

47 - 65 Hz

Input Protection

Over Current Thermal Fuse, Surge Protection

OUTPUT

Voltage

380 / 400 / 415 VAC RMS ± 1% ~ 3%

Overload Operation

20 ms. at 500% load

Correction Speed

~1000 V / s

Regulation Speed

5000 V / s

Response Time

~ 20 ms.

Output Protection

Short Circuit, Overload, Turning OFF of output over the Output Set Voltage

Short Circuit

630 A ( via Pole Charge Switch)

GENERAL

Technology

RISC Microprocessor Controlled, Full Automatic, Electronics Design with Static Semi Conductors

No Moving Parts Inside

Efficiency

> 98% ( at Full Load )

Mechanic By-Pass

Utility – Regulator Selector PAKO Breaker

CONTROL PANEL

Display

4 x 20 Character LCD Display

Warning Messages

Mains Low / Mains High, Output Low / Output High, Load >100% and Over Temperature

Monitorable Datas

Output Voltage, Input Voltage, Load Percentage

COMMUNICATION

Remote Monitoring

Monitoring of Operation over Network/LAN ( Optional )

ENVIRONMENT

Operating Temperature Range

-10 ˚C / 50 ˚C

Storage Temperature

-25 ˚C / 60 ˚C

Relative Humidity

< 90% , DIN ( 40040 )

Altitute

≤ 2000 m

Noise

< 50 dB ( from 1 meter distance )

Protection Level / Colour

IP20

STANDARDS / CERTIFICATES

International Standards/Certificates

ISO 9001:2008 / EN 50091-1 (Safety) / EN 50091-2 (EMC)

DIMENSIONS

W x D x H (cm)

140 x 120 x 165

Weight (kgs)

1250