RL - 440 KVA

Standard Features

- 4 Stroke, 1500 RPM, water cooled heavy duty diesel engine

- Protection system on manuel run

- Flexible oil pipes and oil draining valve

- Pre-heater

- Lubrication oil and anti-freeze

- 4 Poles, synchrontype, single bearing, brushless alternatör

- Batteries and cables

- Electrostatic paint coated, steel, welded chassis

- Fuel tank housed in the chassis.

- Industrial type silencer

- Electronic battery charger

- Electrical wiring diagram

- User manual and operating manual

 

Optional Features

- Soundproof canopy

- Automatic transfer switch

- Circuit breaker

- Trailer

- External fuel tank

- Heating system for fuel tank

- Oil heater

- Fuel filling system ( Automatic / Manuel )

- Analog indicators

- 1 Phase - 3 Phase switch plugs

- Alarm system for fuel level

- Remote control and monitoring

 

Stand By Power : Supplying of emergency electrical power at variable load, in the event of normal utility power failure. This rating is maximum power, no overload capability is available.

Prime Power : Supplying of electrical power at variable load for an unlimited number of hours in the event of normal utility power failure. 10% over load capability is available.

GROUP

Stand-by Power

440(352)

kVA (kW)

Prime Power

396(316,8)

kVA (kW)

Power Factor

0,8

Cos Phi

Frequency

50 

Hz

 

ENGINE

Make

RICARDO

Model

ST12D-330

Speed

1500

Rpm

Prime Power

330 (448)

kW (HP)

Stand-by Power

366 (497)

kW (HP)

Number of Cylinders

6

Cylinder Combination

 In-Line

Air Indication System

 Turbocharged, Intercooler

Cooling System

 Water Cooler

Governor Type

Electronic

Cylinder Displacement

17,2

lt

Bore ve Stroke

6-144x165

mm

Compression Ratio

17,5:1

Electric System

24V(DC) - 105 A

Fuel Consumption %100 Loaded

70

lt / h

Fuel Consumption %75 Loaded

50

lt / h

Fuel Consumption %50 Loaded

45

lt / h

Fuel Tank Capasity

550

Lt

Fuel Type

Diesel

 

ALTERNATOR

Make

SKN

Model

SKND-440

Type

 Synchron, Brushless

Prime Power

396(316,8)

kVA (kW)

Stand-by Power

440(352)

kVA (kW)

Overloaded

1 hour per 12 hours %110, 2 minute %120

Insulation Resistance

Minimum 1800

V

Short Circuit Current

%300 10 Seconds

Isolation Class

H

Drip Proof

IP 23

Voltage

231 / 400 V

Tolerance of Voltage

%0,5

 

DIMENSIONS

Width (None-Cabine / Cabine)

 1200 (1200)

mm

Length (None-Cabine / Cabine)

3000 (3700) 

mm

Height (None-Cabine / Cabine)

1800 (1960) 

mm

Weight (None-Cabine / Cabine)

3500 (3930) 