Lega Plus Model 80 KVA UPS

General Features

Advanced Microprocessor Control

True Online Double Conversion

IGBT Rectifier and Inverter

Real Digital Signal Processor Controlled Transformerless Design

Active Input Power Factor Correction (≥ 0.99)

Low Input THDi <%3 Perfect Generator Compatibility

Low Output THDv <%3 Perfect Energy for your Loads

Low Total Harmonic Distortion Level

Excellent Compability with Different Power Factor Loads

Selectable Input/Output Voltage and Frequency

Wide Input Voltage Range (160 - 260 VAC)

High Efficiency Up To 95%

Ultra High Efficiency with Smart Eco Mode (%98)

Reliable Parallel / Redundant Operation via Load Synchronization

Smart Fan Control

EMI / RFI Filter

Start on Battery Feature (Cold Start)

Short Circuit, High/Low Voltage and Overload Protections

Adjustable Time for Battery Operation

Battery Deep Discharge Protection

Standard Static ve Maintenance By-Pass

Temperature Compensated Battery Charge, Selectable Charge Current

Advanced Fault Identification, 1000 pcs Alert/Event Memory

Advanced Communication Options with RS232 / RS485

100% Made in TURKEY

Environment Friendly Design, The Most Silent in Its Class

Low Installation and Operation Costs

Easy Maintenance and Service

10 Years Spare Part Availability

7/24 Technical Service and Customer Services

 

Optional Features

Advanced Remote Viewing and Management via SNMP

4 Programmable Dry Contacts

GPRS Modem / CAN BUS Communication Options

Easy Scalability with Parallelling

Microprocessor Controlled Smart Battery Management

Customizable Input/Output Options

 

Standards

EN 62040-1 (Safety), EN 62040-2 (EMC)

TSEK, CE, ISO 9001

Model

PLUS SERIES

Power ( kVA )

80 kVA

INPUT

Number of Phases

3 Phases + N + E

Nominal Voltage / No. of Phases

380 VAC / 410 VAC / 415 VAC (3 P + N)

Voltage Range

176 / 280 Vac. ± % 5  (at Full Load)

Nominal Frequency

50 Hz / 60 Hz

Frequency Range

± 10%

Input Power Factor

≥ 99

THDi

< 5%

OUTPUT

Nominal Voltage / No. of Phases

380 VAC / 400 VAC / 415 VAC (3 P + N)

Voltage Tolerance

± 1%

Nominal Frequency

50 Hz / 60 Hz

Frequency Tolerance

50 Hz ± 0,1% / 60 Hz ± 0,1%

Power Factor

0,8

Crest Factor

03:01

THDv

< 2% (Linear Load) < 4% (Non-Linear Load)

Waveform

Pure Sine

Overload Operation

60 min. at 110% load / 10 min. at 125% load /1 min. at 150% load

STATIC BY-PASS

Voltage Range

175 – 253 VAC ( 3 P + N )

Transfer Time

0 ms.

Overload Capacity

150%

BATTERY

Voltage / Quantity

1X62 12V

Type

Maintenance Free Dry Type

Charging Current

Selectable

Temperature Compensated Charge

Microprocessor and Smart Sensor Controlled

GENERAL

Technology

On-Line Double Conversion

Control

SPWM Controlled IGBT Rectifier and Inverter

Efficiency

Up To 95%

Parallel/Redundant Operation

Optional

Protection

Overload, Over Temperature, Input/Output Short Circuit

COMMUNICATION

Display

240 x 320 Graphical LCD ( Touch Screen Display )

Alert / Event Memory

1000 pcs.

Advanced Communication

RS232, 6 Programmable Dry Contacts, GPRS(Optional), SNMP ( Optional )

ENVIRONMENT

Operating Temperature Range

0 ˚C ~ 40 ˚C

Relative Humidity

0% – 95% ( Non-Condensing )

Altitute

≤ 3000 m

Noise

≤ 50 dB

Protection Class

IP20

PHYSICAL SPECIFICATION

Dimensions (W*D*H)

56*82*128 mm

Weight

170 kgs