Lega T Series 120 KVA UPS

General Features

Efficiency Up To 92%

Galvanic İsolation Transformer In Inverter Output

Emergency Shut-Down Switch Connection

Static By-Pass And Service By-Pass Feature

Detailed Data Monitoring And User-Defined Parameter Set- Ting By Means Of LCD İndicator

128 Recorded Event Memory (4000 Alarms)

Calendar And Clock İndicator

By Means Of Advanced Battery Management, Automatic And Manual Battery Test

Superior Performance For Non-Linear Loads (Computer Load)

Testing Communication Contacts By Simulation

 

Optional Features

Remote Monitoring From Networks And RS232 Communication Port To Switch Off Operating Systems Automatically And Safely And Dry Contact Outputs

Tailor-Made İnput/Output Values

SNMP-Compliant MODBUS-Compliant Communication

Parallel Operation Up To 4 Devices

 

Standards

Production With The Quality Assurance System Of CE, TSE, ISO9001 And ISO14001

2-Year System Warranty And 10-Year Spare Part Supply Warranty

MODEL

T SERIES

Power

120

INPUT

Voltage

380 / 400 Vac 3P + N + Ground ±%15

By-pass Voltage

380 / 400 Vac 3P + N ±%1

Frequency

50 Hz. / 60 Hz. ± %5

EMI

EN 62040-2

OUTPUT

Power (kW)

96

Power Factor

0,8

Voltage

380 / 400 VAC 3P + N

Voltage Tolerance

±%1

Voltage Recovery Time

Max. 25msn.

Frequency

50 / 60 Hz

Frequency Tolerance

Line Synchronized ±%2 , Free Running ±%2

± 0,2 self-employment

Efficiency (%100 load)

%90 - 92

Crest Factor

03:01

Overload

%100 - 10 minutes at 125% load

%125 - 1 minutes at 150% load

>%150 load by-pass

Short Circuit Protection

Elektronik Short Circuit Protection

THD

<%3 (linear load)

<%5 (non linear load)

BATTERIES

Type

Full-closed dry type , Maintenance-free, Sealed Lead Acid

Number of Batteries

30

Charge Voltage

405 VDC

End of Discharge Voltage

300 VDC

Operating temperature

25ºC

Battery protection

Automatic Circuit Breaker

Battery test

Automatic Every 72 Hours

GENERAL

Seri Communication

Dry contacts & RS232

Software

T-MON UPS Remote Monitoring and Management Software

Temperature Range

0ºC - 40ºC

Ventilation

Forced cooling

Humidity (Condensing)

<%90

Protection Class

IP20

Working Height

<2000m.

Noise Level

< 65 dBA

Weight Without battery

765

Dimensions (WxDxH)

1110x810x1650

OPTIONS

Input transformer

Galvanic Isolation Transformer at The Input (in external cabinet)

Input THDI

%10 (with 12 Pulse or 18 Pulse rectifier, according to UPS range)

%5 (18 Pulse rectifier, + filter), up to 100kVA)

Input Power Factor

0.95 - 0.98 (18 Pulse redresor with up to 100kVA)

Parallel operation

N+1 (up to 4)

In 18 pulse % 12 pulse applications, the standard chassis dimensions may change

Communication

SNMP, MODBUS, Remote Mon. Panel, RS485