Transformerless UPS Topology
Low Input Current Total Harmonic Distortion (THD)
High Input Power Factor
High Efficiency Up To 94%
Cold Start Function
Static And Maintenance By-Pass Switch
Output Short Circuit And Overload Protection
External REPO Switch Input
192 Events Memory (192 Events 4500 Alarms)
Clock And Calender (Battery Supported)
Automatic Battery Test,Remaining Battery Time Indicator
Temperature Compansated Charge System (Optional)
2 RS232 Serial Ports And 12 Dry Contact Outputs
3 DSP Controlled Modular Structure
Optional SNMP And MODBUS Adaptors
Optional Graphical Panel
Optional USB Flash Memory
Full Digital Structure
Small Footprint
Ecomode Operation (Optional)
Fewer Electronic Components
Output Current Limiting
Advanced Diagnostics For The Input
Selectable Input/Output Voltage/Frequency/Range
Split By-Pass Input (Second Input)
Output DC Leakage Protection
Seperate DSP For Inverter Control
Seperate DSP For The PFC
3 Level Battery Protection
High Charge Current Capacity
Charge/Discharge Current Indicator
Advanced Remote Control
Manufactured According To EC Directive; EN62040
10 Years Spare Parts Support
2 Years Warranty
MODEL |
DSP |
Power (KVA) |
40 kVA |
Power (KW) |
36 kW |
Power Factor |
0,9 |
INPUT |
|
Number of Phases |
3 Phase + Neutral |
Input Voltage |
220/380, 230/400 or 240/415 Vac |
Input Voltage Tolerance |
+20% , -25% (+15% at 240/415Vac) |
Input Power Factor (PF) |
0,98 - 0,99 (at full load) |
Input THDI |
<= 5% (at full load) |
Input Frequency |
50 Hz. ±5% |
By-pass Voltage |
220/380, 230/400 or 240/415 Vac 3 Phase + Neutral |
By-pass Frequency |
50 Hz. ±2% |
RFI Level |
EN62040-2 |
OUTPUT |
|
Number of Phases |
3 Phase + Neutral |
Output Voltage |
220/380, 230/400 or 240/415 Vac |
Output Voltage Tolerance |
±1% |
Output Frequency |
50 Hz. |
Output Frequency Tolerance (Synchronous) |
±2% |
Output Frequency Tolerance (Battery) |
±0,2% |
Efficiency (100% Load) |
up to 94% |
Load Crest Factor |
3:1 |
Output Voltage THD (linear load) |
<3% |
Overload |
125% Load 10min. , 150% Load 1min. |
BATTERY |
|
Total Number |
60 blocks 12V (2x30 serial 60 batteries) |
Float Charge Voltage (250C) |
± 405V DC |
End of Discharge Voltage |
± 300V DC |
Battery Test |
Automatic and Manual |
Boost Charge |
Available |
COMMUNICATION INTERFACES |
|
RS232 Com Port |
2 each standard (COM1 and COM2) |
External Temperature Measurement Input |
Available (standard) |
RS485 Comm. Port |
Optional |
Remote Monitoring Panel |
Optional |
SNMP Adapter |
Optional |
Modbus Adapter |
Optional |
Alarm Relay Contacts |
4 each dry contacts (function programmable) 8 optional |
Digital Inputs |
2 each optional |
Emergency Power-Off Input |
Available (standard) |
ENVIRONMENT |
|
Operating Temperature |
0 – 400C |
Operating Humidity |
<= %90 (non-condensing) |
Acoustic Noise |
<62dB |
Dimensions (WxDxH) (mm) |
515 x 855 x 1450 |
Device Type and Protection Class |
Class 1 – IP20 |
Weight (Without Batteries) (app. kgs) |
175 |