PTL - 55 kVA

Standard Features

- 4 Stroke, 1500 RPM, water cooled heavy duty diesel engine

- Protection system on manuel run

- Flexible oil pipes and oil draining valve

- Pre-heater

- Lubrication oil and anti-freeze

- 4 Poles, synchrontype, single bearing, brushless alternatör

- Batteries and cables

- Electrostatic paint coated, steel, welded chassis

- Fuel tank housed in the chassis.

- Industrial type silencer

- Electronic battery charger

- Electrical wiring diagram

- User manual and operating manual

 

Optional Features

- Soundproof canopy

- Automatic transfer switch

- Circuit breaker

- Trailer

- External fuel tank

- Heating system for fuel tank

- Oil heater

- Fuel filling system ( Automatic / Manuel )

- Analog indicators

- 1 Phase - 3 Phase switch plugs

- Alarm system for fuel level

- Remote control and monitoring

 

Stand By Power : Supplying of emergency electrical power at variable load, in the event of normal utility power failure. This rating is maximum power, no overload capability is available.

Prime Power : Supplying of electrical power at variable load for an unlimited number of hours in the event of normal utility power failure. 10% over load capability is available.

GROUP

Stand-by Power

55 (44)

kVA (kW)

Prime Power

49,5 (39,6)

kVA (kW)

Power Factor

0,8

Cos Phi

Frequency

50

Hz

 

ENGINE

Make

PENTA

Model

P4102

Speed

1500

rpm

Prime Power

42 (52,5)

kW (HP)

Stand-by Power

46 (57,5)

kW (HP)

Number of Cylinders

4

Cylinder Combination

 In-Line

Air Indication System

 Turbo Charge

Cooling System

 Water Cooled

Governor Type

Mechanic

Cylinder Displacement

2,38

Lt

Bore ve Stroke

102 x 118

Mm

Compression Ratio

19,5:0,5

Electric System

12 V(DC) - 60 A

Fuel Consumption %100 Loaded

11,7

lt / h

Fuel Consumption %75 Loaded

9,5

lt / h

Fuel Consumption %50 Loaded

6

lt / h

Fuel Tank Capasity

180

Lt

Fuel Type

Dizel

 

ALTERNATOR

Make

SKN

Model

SKNB-55

Prime Power

49,5 (39,6)

kVA (kW)

Stand-by Power

55 (44)

kVA (kW)

Overloaded

1 hour per 12 hours %110 2 minute %120

Insulation Resistance

Minimum 1800

V

Short Circuit Current

%300 10 seconds

Isolation Class

H

Drip Proof

IP 23

Voltage

231 / 400 V

Tolerance of Voltage

 %5

 

DIMENSIONS

Width (None-Cabine / Cabine)

1000 (1000)

mm

Length (None-Cabine / Cabine)

1900 (2500)

mm

Height (None-Cabine / Cabine)

1300 (1650)

mm

Weight (None-Cabine / Cabine)

900 (1050)

kg